Laserfiche WebLink
.�.__ . , . ._ . ... : ..__ .. ._ . .. .. . _ <br /> . . �� <br /> � �' <br /> Plan Check No. B 59621 <br /> September 4, 1998 <br /> Page 2 of 5 <br /> 2. As the administrative portion of the building is less than 25% (in area) of the storage <br /> occupancy, an occupancy separation is not required per Section 302.1. However, if an <br /> occupancy separation is desired, the metal decking for the floor/ceiling assembly should be <br /> shown protected with a spray-on firecoating or equivulent fire-protection. Section 3023 <br /> 3. The calculated occupant load for the warehouse is 16 persons per Table 29-A. One <br /> designated toilet room for each sex should be provided. Section 29023.1 <br /> 4. It should be clarified whether the mechanical rooms contain a cenual heating plant, boiler, or <br /> hot-water supply builer where the largest piece of equipment exceeds 400,000 Btu per hour <br /> input. Section 302.5 <br /> 5. Toilet rooms accessible to the public should be shown to have walls within 2 ft of the &ont <br /> and sides of water closets finished to a height of 4 ft. with a smooth, hazd, non-absorbent <br /> surface. Section 807.1.2 <br /> Construction <br /> 1. The details, construction notes and a section for the two-hour area scparation wall should be <br /> shown on the plans. Section 504.6 <br /> 2. The roof plan should show the location of the area separation wall below with the 10' wide <br /> zone mazked where no openings aze permitted. Section 504.6.4, Exception 3 <br /> 3. The guazdrail on the Ianding for Stair B shown on sheet A6.1 is required to be no less than 42 <br /> inches high. Exception 3 to Section 509.2 <br /> 4. Class I standpipes are required per Table 9-A. The location of the standpipes should be I <br /> shown on the plans. Section 904.53 I <br /> 5. 'fhe pfans should note that penetrations through fire-resistive walls shall be protected by an <br /> approved penetration firestop system installed as tested in accordance with UBC Standazd 7-5 ' <br /> and shall have an F rating of not less than the rating of the wall penetrated. Section 709.63 <br /> 6. Signs should be displayed permanently near or on each required fire door per Section 713.13 <br /> to read as follows: <br /> FIRE DOOR <br /> DO NOT OBSTRUCT <br /> 7. Safety glazing should be shown for the glazing adjacent to the entry door. Section 2406.4 <br />