Laserfiche WebLink
. . � r � <br /> 4. The mechanical heat sources will be divided into individual floor zones. Since the <br /> storage areas of this building will be semi-heated, each zone heating source will not <br /> exceed 400,000 Btu per hour. <br /> 5. The Uni-sex toilet will have ceramic tile on the floor coved up the wall for 4'on the <br /> front and sides of the water closet See interior elevatlons 5-A6.1. <br /> Construction <br /> 1. A 2-Hour wall sec6on with construction notes has been added to the plans. See <br /> 17/A62. <br /> 2. The roof plan now indicates the 10'zone on no penetrations, 5'each side of G�d J, <br /> the location of the 2-Hour wall. See the roof plan A3.6. <br /> 3. The guardrail on the landing for Stair B is shown at 42'. See Steir Section B, sheet <br /> A6.1. <br /> 4. The Class I standpipes are shown in the stairwells on sheet A/6.1. <br /> 5. All penetradons through fire resistive walls will be protected with a UL listed firestop <br /> system with an F rating cortesponding to the radng of the wall penetrated. See detail, <br /> BIA6.2 <br /> 6. Signs will be displayed on each required fire door stau�g"Fire Door-Do not <br /> ObstrucY. See door notes on the door schedule. <br /> 7. Safety glazing is noted on the glazing adjacent to the entry door. See Southwest <br /> Elevatlon sheet A4.2. <br /> Exiting <br /> 1. Hallways will be designated on the plans. See all Floor plans <br /> 2. A door schedule is provided. See sheet A3.1. <br /> 3. The stair well guard rail is now shown continuing to the roof. See 7/A6.1. <br /> 4. All wall and floor/ceiling assemblies in the stair enclosures are now rated for 2-hours. <br /> See notes on the floor plans and details on A/6.1. <br /> 5. The exit enclosure wall bearing on floodceiling assemblies are tated for 2-hours. See <br /> A16.1 and details on sheet A/6.2. <br /> 6. Since there is no drop ceiling,the protection for the floor assembly that forms a <br /> protective membrane for the stair enclosure will be spray applied fire proofing on the <br /> underside of the floor deck,the supporting beams and columns indepe�dent of the <br /> wall assembly ratings. See A16.1 and details on sheet A/6.2. <br /> 7. The doors into the stair enclosures with a 90 minute rating and a maximum <br /> temperature rise not exceeding 450 degrees. See the door schedule on A/3.1. <br /> 8. An approved barrier is indicated on Stair A1 main level on sheet A3.2. It is detailed <br /> on A16.2 <br /> 9. Exit signs are shown on the exterior doors of the exit enGosures. See PJ3.2 <br /> 10. Stairway identification signs conforming with Section 1003.3.3.13 are detailed on <br /> A16.2 and noted ^t�the enlarged stair plans on A611. <br /> 11. A key for entry into the stairvvells for emergency access will be located in the knox <br /> box already provided and shown on sheet A/32. <br /> 12. A landing of 44" in depth is shown on exterior stair landings. See sheet A/3.2 <br /> 13. The exit lighting is provided with an emergency back up system in wmpliance with <br /> the Electrical Code. See General Note 10, sheet AI0.1. <br /> 14. Back-up system will provide power for 1'/:hours. See General Note 10, A/0.7. <br /> Accessibility <br /> 1. The accessible entrances are noted on sheet A13.1 and A/3.2. <br />