Laserfiche WebLink
Dege ( � <br /> D�en <br /> archiiccture and intcriur dcsign <br /> 3 February 2005 <br /> Mr. Tony R. Lee, Plans Examiner D ���� v LS <br /> City of Everett D <br /> Engineering/Pubic Services DepaRment FEB 0 4 p005 <br /> 320o Cedar Street CITY OF EVER <br /> Everett, WA 98201 Permit Serviees� <br /> Re: Everett Holiday Inn <br /> 3105 Pine Street <br /> Plan Review No.: B0412-038 <br /> Dear Mr. Lee; <br /> Attached please find 2 sets of revised drawings being resubmitted with corrections as <br /> requested in your review letter dated 6 January 2005. Our response to each item is <br /> listed below. <br /> 1. New walls and partitions <br /> Details are not included in this drawing set because none of the new partitions <br /> are required to be rated. ln addition,our CSI Specifications require that all <br /> partitions be metal stud with Type X gypsum wall board, thereby meeting the <br /> requirements for non-combustible construction. <br /> 2. Porte Cochere fire-ratine <br /> See A5.1 for roof rating and UL numbers. <br /> 3. Fire-retardant-treated wood at �arapet sections <br /> See A5.3. All wood will be fire-treated. <br /> 4. One-hour rated suspended ceilinp / rouf assemblies <br /> See A5.1,4&5/A5.4, 1/A5.5. All new roofs are being constructed as 1-hour <br /> assemblies. In addition,the Pool arca is being upgraded to l-hour. <br /> 5. Safety glazing <br /> See A4.1, A4.2, �43, A4.6. A7.1. All glass required to be rated is noted on <br /> the elevations. [n addition, the CSI Specifications have detailed requirements <br /> for complying with [BC safety glazing requirements. <br /> 1402 Third Avenue Suite 1100 Seattle,Washington, USA 98101 <br /> tel 206 623�368 fax 206 623�&548 www.ddseattle.com <br /> Y <br />