PIPING FROST RAIL SYSTEM: <br /> 1 ) . Refrigeration Tech - PLEASE FOLLOW DRAWINGS. <br /> 2) . Line sizes - 1 /2" Liquid and 5/8" Suction lines with 3/4" <br /> thickness insulation on suction line. <br /> 3) . maximum run with one ICE-75 units <br /> 4) . Do not on copper lines that are passing <br /> through the bar top. This will create dead spots at <br /> the joints of the FRails. <br /> 5) . There is not a correct direction for the refrigeration <br /> circuit in the FRails - in and out does not matter. <br /> However, if you feed the circuit on the left side, stay <br /> consistent with all the circuits. <br /> 6) . Position TXV so that feeder tuoes are the same <br /> length. Never cut excess lines coming off the <br /> distributor, simply coil up any extra copoer. <br /> 7) . TXV bulbs needs to be strapped tight, horizontally <br /> at the _ ievei or one o'ciocK position. <br /> 8) . Place the TXV bulb as located on the drawings. You <br /> do not want to place the bulb in a position where <br /> another circuit can influence the circuit that we are <br /> trying to control. <br /> 9). Insulate all suctior lines using 1/4" wall thickness <br /> insulation and use foam insulation tape between <br /> sections and under bar areas. <br /> 10) . If the Refrigeration Unit is mounted above the Frost <br /> Rail, a Refrigeration "P-TRAP is required every 8' of <br /> lift on the Suction Line. <br /> /3 <br />