Laserfiche WebLink
Plan Check qB-43780 <br />March 23, 1994 <br />Page 2 <br />6. The exit corridor on the third floor adjacent to the north exit stair must <br />be closed on each end and the openings must be constructed as outlined <br />in item 5 above. <br />7. Elevator lobbies are required to separate the elevator shaft from stairs <br />and corridors. Sec. 33050) <br />8. One rated construction is required between the equipment room and <br />other spaces on the second floor. Sec. 708. <br />9. All doorways leading to accessible rooms shall have an unobstructed <br />clear width of not less than 32 inches. Sec. 31060). <br />10. Accessible doors shall have maneuvering clearances per Section <br />31060)3. <br />In order for the processing of your application to continue, it will be necessary to <br />provide the Building Division with two complete new sets of drawings reflecting the <br />corrections requested. <br />Upon resubmital of the drawings, your application will be given priority and plan <br />review will recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structure wil! be constructed in compliance with all adopted <br />codes. <br />Sincerel � o <br />e Iv�dFal <br />Associate Engineer/Building <br />WJMpo/77l0 <br />CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (206) 259-8800 • Fax (206) 259-8882 <br />