Structural <br /> 1. It appears that new wall openings are being added to the existing building as well as <br /> new roof framing with a portion of this framing attaching to the existing structure. A <br /> new slab-on-grade is being added for the majority of the building. By inspection, the <br /> proposed work appears to comprise more than 50% of the building area. Per IEBC Sec <br /> 907.4.1, please provide an engineering analysis and evaluation report for seismic forces <br /> acting on the altered structure. <br /> 2. From the submitted permit calculations, it appears that the existing beams labeled G1 <br /> through G4, used a snow loading of 20 psf uniform snow load for evaluation. The <br /> design snow loading is 25 psf uniform non-reducible. Please revise the calculation as <br /> required and provide details for possible strengthening, if required, for gravity framing <br /> members affected by placement of new mechanical units per IEBC Sec 907.3. <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br /> of Washington and adopted by the City of Everett. The current IBC referenced standard for <br /> accessible design is the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> These comments address building issues only. Additional revisions or additions may be required <br /> by other departments (such as Utilities, Traffic, Planning or Fire). All required submittals must <br /> be of sufficient detail and information to ensure that the proposed structure will be constructed <br /> in compliance with all adopted codes. <br /> Sincerely, <br /> Tony Lee <br /> Building Official <br /> Ja es Bronder, PE <br /> Associate Engineer/ Plans Examiner <br /> (g/")) <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8813 • Page 2 <br />